saffire
Features
- Microprocessor based conventional fire alarm control panel complies with EN54-2 & 4
- 8, 10 or 12 detection zones
- One man test facility
- Two sets of volt free changeover contacts operable on fire
- One set of volt free changeover contacts operable on fault
- Head removal via zener clamp or active end of line unit
- Non-latching zones facility
- Class change input
- Zone and alarm disablement
- 28V 125mA fused supply permanently available
- 28V 50mA fused supply available on fire
- Passive repeater available (3 core connection)
Documentation
Part Numbers
| Part No | Panel |
|---|---|
| 05-0015 | Saffire+ 8 Zone |
| 05-0016 | Saffire+ 10 Zone |
| 05-0017 | Saffire+ 12 Zone |
| 05-0000 | Saffire+ 8-12 Passive Repeater |
Specifications
| Saffire+ 8 | Saffire+ 12 | |
|---|---|---|
| Mains Voltage (VAC) | 240 | 240 |
| System Voltage (VDC) | 28.4 | 28.4 |
| Quiescent Current Unsilenced Fault (mA) |
115 | 135 |
| Minimum Battery Size (Ah) 2 x 12V Required |
7 | 7 |
| Detector Voltage (VDC) | 20 | 20 |
| No. of Sense Zones | 8 | 12 |
| Max No. of Detectors per Zone | 30 | 30 |
| Firing Resistance (Ohms) | 510 ± 200 | 510 ± 200 |
| Sense Zone EOL (Ohms) | 3k3 | 3k3 |
| Alarm Voltage (VDC) | 28.4 | 28.4 |
| No. of Alarm Zones | 2 | 2 |
| Max. Alarm Current per Zone (mA) | 300 | 300 |
| Max. No. of Sounders per Zone | 16 | 16 |
| Alarm Zone EOL (Ohms) | 10k | 10k |
| Max. Aux. Supply Current (mA) In Fire Condition |
50 | 50 |
| Max. Permanent 28V Supply Current (mA) |
125 | 125 |
| Panel Weight Inc. Batts. (kg) | 10 | 10 |
| Panel Dimensions (mm) | 335x265x87 | 335x265x87 |
|
|
We reserve the right to change product specifications without notice. Copyright ©VRC Terofire Products 2007. |