saffire
Features
- Microprocessor based conventional fire alarm control panel complies with EN54-2 & 4
- 4 or 6 detection zones
- One man test facility
- Two sets of volt free changeover contacts operable on fire
- Head removal via zener clamp or active end of line unit
- Non-latching zones facility
- Open collector fault output
- class change input
- Zone and alarm disablement
- 28V 50mA fused supply available on fire
Documentation
Specifications
| Saffire+ 4 | Saffire+ 6 | |
|---|---|---|
| Mains Voltage (VAC) | 240 | 240 |
| System Voltage (VDC) | 28.4 | 28.4 |
| Quiescent Current Unsilenced Fault (mA) |
89 | 102 |
| Minimum Battery Size (Ah) 2 x 12V Required |
3 | 3 |
| Detector Voltage (VDC) | 20 | 20 |
| No. of Sense Zones | 4 | 6 |
| Max No. of Detectors per Zone | 30 | 30 |
| Firing Resistance (Ohms) | 510 ± 200 | 510 ± 200 |
| Sense Zone EOL (Ohms) | 3k3 | 3k3 |
| Alarm Voltage (VDC) | 28.4 | 28.4 |
| No. of Alarm Zones | 2 | 2 |
| Max. Alarm Current per Zone (mA) | 300 | 300 |
| Max. No. of Sounders per Zone | 16 | 16 |
| Alarm Zone EOL (Ohms) | 10k | 10k |
| Max. Aux. Supply Current (mA) In Fire Condition |
50 | 50 |
| Max. Permanent 28V Supply Current (mA) |
N/A | N/A |
| Panel Weight Inc. Batts. (kg) | 5 | 5 |
| Panel Dimensions (mm) | 285x230x85 | 285x230x85 |
Part Numbers
| Part No | Description | Picture | Download |
|---|---|---|---|
| 05-0013 | Saffire 4 Zone EN54 Control Panel |
|
VRC Branded UK Manual Unbranded UK Manual Unbranded Portuguese Manual Unbranded Spanish Manual Datasheet |
| 05-0014 | Saffire 6 Zone EN54 Control Panel |
|
VRC Branded UK Manual Unbranded UK Manual Unbranded Portuguese Manual Unbranded Spanish Manual Datasheet |
|
|