Protector 1 and 2 Zone Features


Protector 4 and 6 Zone Features


Documentation


Specifications

  Protector 1 Protector 2 Protector 4 Protector 6
Mains Voltage (VAC) 240 240 240 240
System Voltage (VDC) 28.4 28.4 28.4 28.4
Quiescent Current
Unsilenced Fault (mA)
64 76 89 102
Minimum Battery Size (Ah)
2 x 12V Required
2.2 2.2 3 3
Detector Voltage (VDC) 20 20 20 20
No. of Sense Zones 1246
Max No. of Detectors per Zone 30 30 30 30
Firing Resistance (Ohms) 510 ± 200 510 ± 200 510 ± 200 510 ± 200
Sense Zone EOL (Ohms) 3k3 3k3 3k3 3k3
Alarm Voltage (VDC) 28.4 28.4 28.4 28.4
No. of Alarm Zones 2 2 2 2
Max. Alarm Current per Zone (mA) 200 200 300 300
Max. No. of Sounders per Zone 10 10 16 16
Alarm Zone EOL (Ohms) 10k 10k 10k 10k
Max. Aux. Supply Current (mA)
In Fire Condition
N/A N/A 50 50
Max. Permanent 28V
Supply Current (mA)
N/A N/A N/A N/A
Panel Weight Inc. Batts. (kg) 4.5 4.5 5 5
Panel Dimensions (mm) 285x237x97 285x237x97 285x237x97 285x237x97


Part Numbers

Part No Panel
05-0021 Protector 1 Zone
05-0022 Protector 2 Zone
05-0023 Protector 4 Zone
05-0024 Protector 6 Zone


Valid HTML 4.0 Strict We reserve the right to change product specifications without notice.