VRC Logo

multizone

     Multizone 4-12   Multizone 16-48     

Multizone 16-48 Picture

Features


Documentation


Specifications

  Multizone 16 Multizone 24 Multizone 32 Multizone 40 Multizone 48
Mains Voltage (VAC) 240 240 240 240 240
System Voltage (VDC) 28.4 28.4 28.4 28.4 28.4
Quiescent Current
Unsilenced Fault (mA)
350 440 510 600 660
Minimum Battery Size (Ah)
2 x 12V Required
9 12 Must be calculated for each installation.
Detector Voltage (VDC) 20 20 20 20 20
No. of Sense Zones 1624324048
Max No. of Detectors per Zone 30 30 30 30 30
Firing Resistance (Ohms) 510 ± 200 510 ± 200 510 ± 200 510 ± 200 510 ± 200
Sense Zone EOL (Ohms) 3k3 3k3 3k3 3k3 3k3
Alarm Voltage (VDC) 28.4 28.4 28.4 28.4 28.4
No. of Alarm Zones 4 4 4 4 4
Max. Alarm Current per Zone (mA) 500 500 500 500 500
Max. No. of Sounders per Zone @ 10mA per sounder 50 50 50 50 50
Alarm Zone EOL (Ohms) 10k 10k 10k 10k 10k
Max. Aux. Supply Current (mA)
In Fire Condition
50 50 50 50 50
Max. Permanent 28V
Supply Current (mA)
250 250 250 250 250
Panel Dimensions (mm) 640x395x120 640x395x120 640x395x120 640x395x120 640x395x120


Part Numbers

Part No Description Picture Download
01-0038 Multizone LCD 16 Zone EN54 Control Panel 01-0038 thumbnail VRC Branded UK Manual
Unbranded UK Manual
Datasheet
01-0040 Multizone LCD 24 Zone EN54 Control Panel 01-0040 thumbnail VRC Branded UK Manual
Unbranded UK Manual
Datasheet
01-0042 Multizone LCD 32 Zone EN54 Control Panel 01-0042 thumbnail VRC Branded UK Manual
Unbranded UK Manual
Datasheet
01-0045 Multizone LCD 40 Zone EN54 Control Panel 01-0045 thumbnail VRC Branded UK Manual
Unbranded UK Manual
Datasheet
01-0046 Multizone LCD 48 Zone EN54 Control Panel 01-0046 thumbnail VRC Branded UK Manual
Unbranded UK Manual
Datasheet
01-0050 Multizone LCD 16-48 Zone Repeater Panel - Connection Information