Conventionalback to Saffire LPCB Approved Range

01-0054 | Saffire AP 2 Zone Panel
 
 

Where to Buy

  

Alternative Views (1)click to enlarge

 

 
  • Microprocessor based conventional fire alarm control panel approved to EN54-2 & 4
  • 2, 4, 6 or 8 detection zones
  • One man test facility
  • One set of volt free changeover contacts operable on fire
  • One set of volt free changeover contacts operable on fault
  • Class change input
  • Zone isolate facilities
  • Sounder activation delay (up to 9 minutes)
  • Zone and alarm disablement

2 Zone4 Zone6 Zone8 Zone
Mains Voltage (VAC)240240240240
System Voltage (VDC)24242424
Quiescent Current Unsilenced Fault (mA)48484848
Minimum Battery Size (Ah) 2 x 12V Required7777
Detector Voltage (VDC)21212121
No. of Sense Zones2468
Max No. of Detectors per Zone32323232
Firing Resistance (Ohms)510 ± 200510 ± 200510 ± 200510 ± 200
Sense Zone EOL (Ohms)DiodeDiodeDiodeDiode
Alarm Voltage (VDC)24242424
No. of Alarm Zones2222
Max. Alarm Current per Zone (mA)400400400400
Max. No. of Sounders per Zone20202020
Alarm Zone EOL (Ohms)10k10k10k10k
Panel Weight Inc. Batts. (kg)10101010
Panel Dimensions (mm)335x275