Conventionalback to Saffire Conventional Range

05-0014 | Saffire 6 Zone Panel
 
 

Where to Buy

  

Alternative Views (5)click to enlarge

 

 
  • Microprocessor based conventional fire alarm control panel complies with EN54-2 & 4
  • 4 or 6 detection zones
  • Two set of volt free changeover contacts operable on fire
  • Head removal via zener clamp or active end of line unit
  • Open collector fault output
  • Zone and alarm disablement
  • Class change input
  • Non-latching zones facility
  • One man test facility
  • 28V 50mA fused supply available on fire
 2 Zone 4 Zone 6 Zone 
Mains Voltage (VAC) 240240240
System Voltage (VDC) 28.428.428.4
Quiescent Current Unsilenced Fault (mA) 7689102
Minimum Battery Size (Ah) 2 x 12V Required 2.233
Detector Voltage (VDC) 202020
No. of Sense Zones 246
Max No. of Detectors per Zone 303030
Firing Resistance (Ohms) 510 ± 200 510 ± 200 510 ± 200 
Sense Zone EOL (Ohms) 3k3 3k3 3k3 
Alarm Voltage (VDC) 28.428.428.4
No. of Alarm Zones 222
Max. Alarm Current per Zone (mA) 200300300
Max. No. of Sounders per Zone 101616
Alarm Zone EOL (Ohms) 10k 10k 10k 
Max. Aux. Supply Current (mA) In Fire Condition N/A 5050
Max. Permanent 28V Supply Current (mA) N/A N/A N/A 
Panel Weight Inc. Batts. (kg) 4.555
Panel Dimensions (mm) 234x225x85 285x230x85